MRMV4 Motor protection

Product detail

Product code:
MRMV4
Price
Request a quote Select options below to request a price.

Product Information

Download Area

Available options

Documentation (Brochures & Manuals)

Operating Software Smart view: Documentation & Setup

Application

The MRMV4 is a protection relay which uses the latest Dual-Core-Processor Technology to provide precise and reliable protective functions. Also it is very easy to operate.

The MRMV4 provides all necessary functions to protect low and medium voltage motors at all power levels.

The protection functions are based on current and voltage measurement and supervise all thermal conditions, motor start sequence, stall and locked rotor, undercurrent and incomplete sequence.

Overcurrent functions and earth fault functions are also available as power protection, frequency and voltage elements.

The motor operation can be monitored by statistic and trend recorders.

The protection functions of the MRMV4 have been adapted to comply with the requirements of the VDE-AR-N-4110:2018.

Functional Overview

MRMV4 Functional Overview

Approvals

UL File Nr.: E217753

certified regarding UL508 (Industrial Controls)

CSA File Nr.: 251990

certified regarding CSA-C22.2 No. 14 (Industrial Controls)

EAC

certified by EAC (Eurasian Conformity)

KESCO

동일성 선언서 (Declaration of Identity)

  • Complies with IEEE 1547‑2003

  • Amended by IEEE 1547a‑2014

  • Complies with ANSI C37.90‑2005

  • Complies with “Engineering Recommendation G59 Issue 3 Amendment 4 – July 2018”

  • Complies with “Engineering Recommendation G99 Issue 1 Amendment 3 – May 2018”

Key Benefits of the HighPROTEC MRMV4

  • Wide range power supply: 24 … 270 VDC / 48 … 230 VAC

  • VT measurement from 0 V up to 800 VAC

  • CT measurement always with 1 A and 5 A

  • Plausibility verification intelligence

  • Optimized functional overview by hiding unused functions, parameter and assignments

  • On-board testing without removing the wiring

  • Menu Languages supported: English, German, Spanish, Portuguese, French, Russian, Polish, Romanian


Application

  • Start Cycle Supervision

  • Overload

  • Jam / Locked Rotor

  • Underload

  • Unbalanced Load

  • Number of Starts, Counters,…

  • Keeping motor load under the Thermal Damage Curve

Inputs and Outputs
Analog outputs 4
Binary inputs 8
Current transformer inputs 4
Output relays 6 (12)
Voltage transformer inputs 4
Watchdog relay 1
Protection ANSI
Voltage protection 27/59
Time overcurrent protection 50/51
Earth fault protection 50N/51N
Sensitive EF isolated/compensated 50Ns/51Ns (Option)
Resistance earthed / solidly earthed 50N/51N
Circuit breaker failure protection 50BF
Residual voltage 59N
Phase balance 47
Frequency protection 810/81U
Power direction 32/37
Negative sequence protection 46
Motor protection: locked rotor 51
Motor protection: incomplete start 48
Motor protection: max. number of starts 66
Motor protection: undercurrent 37
Motor protection: thermal protection 49
Supervision ANSI
Current transformer supervision 60L
Voltage transformer supervision 60FL
Trip circuit resp. control circuit supervision 74TC
Additional Features
Control and detection of switchgears
Control and supervision of a circuit breaker
Disturbance recorder
Event recorder
Fault recorder (none volatile)
Parameter sets 4
Programmable Logic
Communication
DNP3 RTU (Option)
DNP3 TCP (Option)
IEC 60870-5-103 (Option)
IEC 60870-5-104 (Option)
IEC 61850 (Option)
IRIG-B00X
Modbus (TCP) (Option)
Modbus RTU (Option)
Profibus DP (Option)
Mounting Type
Housing suitable for 19” rack mounting (Option)
Housing suitable for door mounting