MRI1-IE Time overcurrent relay with Multi-Characteristic

Product detail

Product code:
MRI1
Price
Request a quote Select options below to request a price.

Product Information

Download Area

Available options

Documentation (Brochures & Manuals)

General HighTECH Line User Manual

The MRl1 digital multifunctional relay is a universal time overcurrent and earth fault protection device intended for use in medium-voltage systems, either with an isolated/compensated neutral point or for networks with a solidly earthed/resistance-earthed neutral point.

The protective functions of MRI1 which are implemented in only one device are summarized as follows:

  • Independent (Definite) time overcurrent relay.

  • Inverse time overcurrent relay with selectable characteristics.

  • Integrated determination of fault direction for application to doubly infeeded lines or meshed systems.

  • Two-element (low and high set) earth fault protection with definite or inverse time characteristics.

  • Integrated determination of earth fault direction for application to power system networks with isolated or arc suppressing coil (Peterson coil) neutral earthing. (ER/XR-relay type).

  • Integrated determination of earth short-circuit fault direction in systems with solidly-earthed neutral point or in resistance-earthed systems (SR-relay type).

  • Furthermore, the relay MRI1 can be employed as a back-up protection for distance and differential protective relays.

Benefits and Key Features

  • 19“ racks – fully withdrawable

  • Door mounting – withdrawable and sealable

  • Panel mounting – fully withdrawable

  • Fault / disturbance recorder

  • Intuitive HMI

  • Display (of primary values)

  • Easy setting software – Smart view

  • Compact form factor


Application

  • Interconnection of renewable energies (DER – distributed energy resources) to the public grid.

  • Protection of High, Medium and Low Voltage feeders against thermal damages by overload or short circuit currents.

Inputs and Outputs
Binary inputs 2
Current transformer inputs 4
Output relays 4
Watchdog relay 1
Protection ANSI
Time overcurrent protection 50/51
Earth fault protection 50N/51N
Circuit breaker failure protection 50BF
Additional Features
Fault recorder (none volatile)
Parameter sets 1
Communication
Modbus RTU (Option)
RS485 Open Data Protocol (Option)
Mounting Type
Housing is withdrawable
Housing suitable for door mounting
Housing suitable for mounting plate

© 2022 SEG ELECTRONICS GMBH | All rights reserved
webstránky | webdesign | eshopy | bajan.sk
Website uses cookies
We use cookies to ensure that we give you the best experience on our website. If you continue to use this site we will assume that you are happy with it. Learn More