XI1-I Overcurrent and Short-Circuit Protection Relay

Product detail

Product code:
XI1I
Price
Request a quote Select options below to request a price.

Product Information

Download Area

Available options

Documentation (Brochures & Manuals)

As an universal time overcurrent protection, the XI1I relay of the PROFESSIONAL LINE is generally used in radial and meshed systems. Among other, it is applied as:

  • selective overload and short-circuit protection relay for electr. machines, lines and networks, or for
  • load dependent connection and disconnection of consumers and electric power generators.

It is possible to select from the following tripping characteristics:

  • Definite time overcurrent protection (DMT)

  • Inverse time overcurrent protection (IDMT) with selectable tripping characteristics

    • Normal Inverse

    • Very Inverse

    • Extremely Inverse

Furthermore, the XI1I can be employed as a backup protection for differential and distance protection relays.

Connection XI1I

Definite-Time Overcurrent Protection

Parameter Setting Range
I> 0.5 … 2 × I n (cont.)
I>> 1 … 15 × I n (cont.)
tI> 0 … 1 s / 0 …10 s / 0 …100 s (⌨) (cont.)
tI>> 0 … 2.5 s (cont.)

(⌨) Different setting ranges via DIP switches. ( Smart view covers the whole range.)

Inverse-Time Overcurrent Protection

Tripping characteristics according to IEC 255‑4 or BS 142

Parameter Setting Range
I> 0.5 … 2 × I n (cont.)
I>> 1 … 15 × I n (cont.)
tI> 0.1 … 2 s (cont.)
tI>> 0 … 2.5 s (cont.)

Auxiliary Voltage

Voltage supply via wide-range power supply unit:

Auxiliary voltage range

19 … 390 V DC or

36 … 275 V AC (f = 40 … 70 Hz)

Power consumption

approx. 4 W (terminals A1 and A2)

Benefits of the Professional Line

  • Fast DIN rail mounting    easy and fast mounting
  • Sealable plastic covers    safe (see if anybody has broken the seal)
  • Super easy settings via front buttons    fast without computer
  • LED and output relays fault indication    easy to find out what has happened
  • Compact form factor    fits in small spaces
  • IT security    no way to attack via Ethernet
  • Robust and reliable    well proven reliable quality
  • Wide Range Power Supply    don’t worry about available supply voltage
  • Integrated Self-Test Procedure (via button)    fast and easy checks: relays, LEDs
  • For all relays except XD1-G and except XRI...: optional interface adapter XRS1 (order code XRS1A or XRS1*);

    for all XRI... [except XD1-G]: optional adapter RS485 to USB (order code RSC2485USB1):

      easy doing high precision settings via Windows ® PC software »Smart view«


Application

  • Interconnection of renewable energies (DER – distributed energy resources) to the public grid.

  • Protection of High, Medium and Low Voltage feeders against thermal damages by overload or short circuit currents.

Inputs and Outputs
Current transformer inputs 3
Output relays 2
Protection ANSI
Time overcurrent protection 50/51
Mounting Type
Housing suitable for DIN rail mounting

© 2022 SEG ELECTRONICS GMBH | All rights reserved
webstránky | webdesign | eshopy | bajan.sk
Website uses cookies
We use cookies to ensure that we give you the best experience on our website. If you continue to use this site we will assume that you are happy with it. Learn More